Amps
-
Voltage
-
Frequency
50,60 Hz
Certification
N/A
Segmentation
PRODUCT Detail
Overview
Specifications
Features
Brochures
Governor regulation class | ISO 8528 |
Voltage regulation, no load to full load | +/- 0.5% |
Random voltage variation | +/- 0.5% |
Frequency regulation | Isochronous |
Random frequency variation | +/- 0.25% |
EMS Compatibility | EN61000-4-6/EN61000-6-2 |
- Cummins heavy-duty engine – Rugged 4-cycle industrial diesel delivers reliable power, low emissions and fast response to load changes.
- Permanent Magnet Generator (PMG) – Offers enhanced motor starting and fault clearing short circuit capability.
- Alternator – Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings; low waveform distortion with non-linear loads, fault clearing short-circuits capability, and class H insulation.
- Cooling system – Standard integral set- mounted radiator system, designed and tested for rated ambient temperatures, simplifies facility design requirements for rejected heat.
- Control system – Standard PowerCommand® electronic control provides total system integration including remote start/stop, precise frequency and voltage regulation, alarm and status message display, AmpSentryTM protection, output metering, auto-shutdown.
- Enclosures – Optional sound attenuated enclosure is available.
- Motorized circuit breaker – Optional 3 or 4 pole motorized circuit breaker available.
- Warranty – Backed by a comprehensive warranty and worldwide distributor network.
- ISO 8528-5 G3 Capable – Refer to factory for site and configuration specific transient performance classification